Online UPS SANUPS RMA
RMA500T3
- Parallel redundancy
- Vertical type
- Input terminal block
- Output terminal block
For illustrative purposes only
Specifications
- Model No.
- RMA500T3
- UPS topology
- Double conversion online
- No. of input phases/wires
- 3-phase 3-wire
- Rated input voltage[V]
- 200
- Input voltage range
- ±15% of rated voltage
- Rated input frequency[Hz]
- 50/60
- Input frequency range
- Within ±5% of rated frequency
- Input power factor
- 0.97 or greater (lagging)
- No. of output phases/wires
- 3-phase 3-wire
- Rated output capacity[kVA]
- 50
- Rated output capacity[kW]
- 45
- Rated output voltage[V]
- 200
- Output voltage regulation
- Within ±2% of rated voltage
- Rated output frequency[Hz]
- 50/60
- Output transient voltage fluctuation
- At abrupt input voltage change: ±2% of rated voltage (For loss or return of input power / for ±10% voltage changes) At abrupt load change: Within ±5% of rated voltage (For 0⇔100% load step changes) At output transfer: Within ±5% of rated voltage (At the time of transfer from bypass to inverter, at rated output)
- Output overcurrent protection
- Uninterrupted transfer to bypass at approx. 150% or more (With automatic retransfer function)
- Output overload capability
- Inverter: 125% (for 10 min), 150% (for 1 min); at rated input and rated load power factor Bypass: 200% (for 30 s), 800% (for 2 cycles); at rated input and rated load power factor
- Inverter
- High-frequency PWM
- Energy storage device type
- Small-sized valve-regulated lead-acid (VRLA) battery
- Standard backup time[min]
- 10
- Cooling method
- Forced air cooling
- Operating temperature range
- 0 ~ +40℃
- Operating humidity range
- 30 to 90% (non-condensing)
- Acoustic noise[dB]
- 60
- Heat dissipation[W]
- 8800
- Mass[kg]
- 2400