Online UPS SANUPS A23C
A23C104
- Eco Products
- Vertical type
- Input terminal block
- Output terminal block
For illustrative purposes only
Specifications
- Model No.
- A23C104
- UPS topology
- Double conversion online
- No. of input phases/wires
- 3-phase 3-wire
- Rated input voltage[V]
- 200/210
- Input voltage range
- 200 V: Within ±15% of rated voltage, 210 V: Within ±10%
- Rated input frequency[Hz]
- 50/60
- Input frequency range
- Within ±5% of rated frequency
- Input power factor
- 0.98 or greater (at rated output)
- No. of output phases/wires
- 3-phase 3-wire
- Rated output capacity[kVA]
- 100
- Rated output capacity[kW]
- 90
- Rated output voltage[V]
- 200/210
- Output voltage regulation
- 200 V: Within ±1% of rated voltage, 210 V: Within ±2% (at AC input operation)
- Rated output frequency[Hz]
- 50/60
- Output frequency regulation
- Within ±0.01% of rated frequency (In free-running oscillation)
- Output transient voltage fluctuation
- Abrupt input voltage change: ±2% of rated voltage (For loss or return of input power) Abrupt load change: 200 V: Within ±3% of rated voltage, 210 V: Within ±5% (For 0⇔100% load step changes) At output transfer: 200 V: ±3% of rated voltage, 210 V: Within ±5% (At the time of transfer from bypass to inverter, at rated output)
- Output overcurrent protection
- Uninterrupted transfer to bypass at approx. 150% or more (With automatic retransfer function)
- Output overload capability
- Inverter: 125% (for 10 min), 150% (for 1 min) Bypass: 200% (for 30 s), 800% (for 2 cycles)
- Inverter
- High-frequency PWM
- Energy storage device type
- Small-sized valve-regulated lead-acid (VRLA) battery
- Standard backup time[min]
- 10
- Cooling method
- Forced air cooling
- Operating temperature range
- 0 ~ +40℃
- Operating humidity range
- 30 to 90% (non-condensing)
- Acoustic noise[dB]
- 65dB以下
- Heat dissipation[W]
- 8700
- Mass[kg]
- 2690
Related Information
Options
Item Name |
---|
Input/Output panel with external maintenance bypass circuit, top cable entry (TRA23C104T□) |
Input/Output panel with external maintenance bypass circuit, bottom cable entry (TRA23C104B□) |
Input/Output panel with Scott-T transformer circuit, top cable entry (TRA23C104T□□□) |
Input/Output panel with Scott-T transformer circuit, bottom cable entry (TRA23C104B□□□) |