Hybrid UPS - SANUPS E11A-Li
E11AL351B021
- Vertical type
- Input plug
- Output outlet

For illustrative purposes only
Specifications
- Model No.
- E11AL351B021
- UPS topology
- Hybrid
- No. of input phases/wires
- Single-phase 2-wire
- Rated input voltage[V]
- 100/110/115/120
- Input voltage range
- In Double Conversion mode: 80 to 115 V
In Active Filter mode: 95 to 105 V
In Economy mode: Within ±8% of rated voltage (±5% in automatic setting)
- Rated input frequency[Hz]
- 50/60
- Input frequency range
- In Double Conversion mode: Within ±8% of rated frequency
In Active Filter mode: Within ±1, 3, or 5% of rated frequency
In Economy mode: Within ±1, 3, or 5% of rated frequency
- Input power factor
- 0.95 or greater
- Required input capacity[kVA]
- 0.358
- No. of output phases/wires
- Single-phase 2-wire
- Rated output capacity[kVA]
- 0.35
- Rated output capacity[kW]
- 0.245
- Rated output voltage[V]
- 100/110/115/120
- Output voltage regulation
- In Double Conversion mode: Within ±2% of rated voltage
In Active Filter mode: Within -7% to +5% of rated voltage
In Economy mode: Within -10% to +8% of rated voltage (-7% to +5% in automatic setting)
- Rated output frequency[Hz]
- 50/60
- Output frequency regulation
- During grid operation
In Double Conversion mode fixed setting: Within ±1% of rated frequency
In automatic transfer setting: Within ±1/3/5% of rated frequency (Factory setting: ±3%)
During battery operation
Within ±0.5% of rated frequency (This applies in asynchronous operation too)
- Output transient voltage fluctuation
- For abrupt load change: Within ±5% of rated voltage (For 0⇔100% load step changes at rated input)
For loss/return of input power: Within ±5% of rated voltage (At rated output)
For abrupt input voltage change: Within ±5% of rated voltage (For ±10% abrupt change)
- Output overcurrent protection
- Breaker protection
- Output overload capability
- 200% (for 30 s), 800% (for 2 cycles)
- Energy storage device type
- Lithium-ion battery
- Expected battery (device) life
- At 50% load level: Approx. 10 years
At rated load level: Approx. 7 years
- Standard backup time[min]
- 8
- Cooling method
- Forced air cooling
- Operating temperature range
- 0 ~ +40℃
- Operating humidity range
- At 50% load level: 10 to 90% (non-condensing)
At rated load level: 10 to 90% (non-condensing)
- EMC standard
- EN 62040-2 C2:2006
EN 55022:2006 Class-A
(FCC Part15 Sub partB Class A, CISPR 22 Class A, VCCI Class A)
- Acoustic noise[dB]
- 38
- Heat dissipation[W]
- 59
- Remarks
- Interface
PC port: RS-232C
Network support: Optional LAN interface card box is required
Related Information
Options
Item Name |
---|
Air filter (FL003) |