SANYO DENKI(山洋電気) PRODUCTS

SANUPS Hybrid UPS - SANUPS E11B-Li
E11BL202A012AUJ

  • Eco Products
  • Vertical type
  • Rack mount type
  • Input plug
  • Output outlet
  • UL standard
  • CE marking
  • UKCA

For illustrative purposes only

Specifications

Model No.
E11BL202A012AUJ
UPS topology
Hybrid
No. of input phases/wires
Single-phase 2-wire
Rated input voltage[V]
200/208/220/230/240
Input voltage range
During Double Conversion mode
  At load level < 40% ... 110 to 300 V
  At load level < 70% ... 136 to 280 V
  At load level ≥ 70% ... 160 to 280 V
During Economy mode
  Within ±8% of rated voltage
Rated input frequency[Hz]
50/60
Input frequency range
In Double Conversion mode fixed setting
  Within ±1% of rated frequency (Synchronization range)
  40 to 120 Hz (Asynchronous operation range)

In automatic transfer setting
  Within ±1/3/5% of rated frequency (Factory setting is ±3%, synchronization range)
  40 to 120 Hz (Asynchronous operation range)
Input power factor
0.95 or greater
Required input capacity[kVA]
2.2
No. of output phases/wires
Single-phase 2-wire
Rated output capacity[kVA]
2
Rated output capacity[kW]
1.6
Rated output voltage[V]
200/208/220/230/240
Output voltage regulation
Double Conversion mode: Within ±2% of rated voltage
Economy mode: Within -10% to +8% of rated voltage
Rated output frequency[Hz]
50/60
Output frequency regulation
In Double Conversion mode fixed setting: Within ±1% of rated frequency
In automatic transfer setting: Within ±1/3/5% of rated frequency (Factory setting: ±3%)

During battery operation: Within ±0.5% of rated frequency (This applies in asynchronous operation too)
Output transient voltage fluctuation
At abrupt load change: Within ±5% of rated voltage (For 0⇔100% load step changes)
At loss/return of input power: Within ±5% of rated voltage (At rated output)
At abrupt input voltage change: Within ±5% of rated voltage (For ±10% voltage changes)
Output overcurrent protection
Automatic transfer to bypass (With automatic retransfer function)
Output overload capability
Inverter: 105% (for 200 ms)
Bypass: 200% (for 30 s), 800%(for 2 cycles)
Energy storage device type
Lithium-ion battery
Expected battery (device) life
Approx. 10 years
Standard backup time[min]
4
Cooling method
Forced air cooling
Operating temperature range
-10 ~+55℃
Operating humidity range
20 to 90% (non-condensing)
EMC standard
VCCI 32-1 Class A
FCC Part15 Sub partB Class A
EN62040-2 C2: 2010,
EN55022: 2010 Class A,
EN62040-2: 2006,
EN55024: 2010
Acoustic noise[dB]
55
Heat dissipation[W]
260
Mass[kg]
18

Download Materials List

Materials Material No. File Size Download Link
取扱説明書 M0020198 8.8 MB Login required
ユーザ設定説明書 M0020196 8.0 MB Login required
Instruction Manual M0020199 8.8 MB Login required
Setting Menu Manual M0020197 8.0 MB Login required
Manuel d'utilisation M0020362 9.0 MB Login required
Manuel des menus de réglage M0020389 8.6 MB Login required

If there are any differences in the descriptions in Japanese, English or French, Japanese shall prevail.

Applicable Models

Model no. Item Name
PMS52A00DL UPS management software (Windows version) SANUPS SOFTWARE Download version
PMS52A00DL-10 UPS management software (Windows version, 10 licenses) SANUPS SOFTWARE Download version
PMS52A00DL-100 UPS management software (Windows version, 100 licenses) SANUPS SOFTWARE Download version
PMS52A00DL-50 UPS management software (Windows version, 50 licenses) SANUPS SOFTWARE Download version
PMS53A00DL UPS management software (Multi-OS version) SANUPS SOFTWARE Download version
PMS53A00DL-10 UPS management software (Multi-OS version, 10 licenses) SANUPS SOFTWARE Download version
PMS53A00DL-100 UPS management software (Multi-OS version, 100 licenses) SANUPS SOFTWARE Download version
PMS53A00DL-50 UPS management software (Multi-OS version, 50 licenses) SANUPS SOFTWARE Download version
PRCONIF007 Dry contact interface card (Terminal block)
PRCONIF008 Dry contact interface card (D-sub 15-pin)
PRLANIF013B Power Management Product - LAN Interface Card (Supports IPv6 and temperature/humidity sensors)
PRLANIF022A Power Management Product - LAN Interface Card (IPv6, Modbus TCP supported, with cover)
PRLANIF024A Power Management Product - LAN Interface Card (IPv6, Modbus TCP/RTU supported, with cover)

Related Information

Options

Item Name
Vertical stands (STAND2UA00)
2U rack support rails (RM030)
Contacts
  •  
License Agreement

This license agreement is a legal agreement between the customer and SANYO DENKI CO., LTD. and its subsidiaries (hereinafter referred to as "SANYO DENKI Group") regarding SANYO DENKI CO., LTD. software (hereinafter referred to as "the software").

The customer may download this software only upon consenting to this agreement.

1. License Grants

SANYO DENKI Group grants the customer the nonexclusive right to use this software. The customers may use, install, and update the software while using the product purchased from the SANYO DENKI Group.

The customer may not lend or transfer this software to a third party nor offer it as collateral without obtaining prior written approval from SANYO DENKI Group. In addition, if the customer lends or transfers the software to a third party with prior written approval of SANYO DENKI Group, the customer must ensure that the third party complies with the provisions of this agreement.

2. Copyrights and Intellectual Property Rights

SANYO DENKI retains all copyrights, patent rights, trademark rights, know-how, and all other intellectual property rights related to this software and relevant printed materials (including electronic media).

3. Warranty Coverage

SANYO DENKI Group guarantees the operation and functions described in the instruction manual for this software. However, the warranty does not cover the software in the following cases:

  1. (1) The software is used in unsupported operating environments or with unsupported products.
  2. (2) The software is used in a manner other than as specified in the instruction manual.
  3. (3) The software is modified.
4. Legal Disclaimer

SANYO DENKI Group and its distributors are not liable for any damages outside the scope of warranty as stated in this license agreement.

SANYO DENKI Group is not responsible for any malfunction caused by installing or updating this software in unsupported operating environments or with unsupported products.

5. Jurisdiction

Any disputes arising in the fulfillment of this agreement shall be settled by the Tokyo District Court as the exclusive competent court.

6. Governing Law

This agreement shall be governed by the laws of Japan.

  • No match product found.

  • No match product found.

  • Processing was interrupted because the number of displayed items was exceeded. Add the filter condition and re-execute

  • Loading... Please Wait