Hybrid UPS SANUPS E11B
E11B102A001AMUJ
- Eco Products
- Vertical type
- Rack mount type
- Input plug
- Output outlet
- UL standard
- CE marking
- UKCA
For illustrative purposes only
Specifications
- Model No.
- E11B102A001AMUJ
- UPS topology
- Hybrid
- No. of input phases/wires
- Single-phase 2-wire
- Rated input voltage[V]
- 100/110/115/120
- Input voltage range
- During Double Conversion mode
At load level < 40% ... 55 to 150 V
At load level < 70% ... 68 to 144 V
At load level ≥ 70% ... 80 to 144 V
During Economy mode: Within ±8% of rated voltage
- Rated input frequency[Hz]
- 50/60
- Input frequency range
- In Double Conversion mode fixed setting
Within ±1% of rated frequency (Synchronization range)
40 to 120 Hz (Asynchronous operation range)
In automatic transfer setting
Within ±1/3/5% of rated frequency (Factory setting is ±3%, synchronization range)
40 to 120 Hz (Asynchronous operation range)
- Input power factor
- 0.95 or greater
- Required input capacity[kVA]
- 1.1
- No. of output phases/wires
- Single-phase 2-wire
- Rated output capacity[kVA]
- 1
- Rated output capacity[kW]
- 0.8
- Rated output voltage[V]
- 100/110/115/120
- Output voltage regulation
- Double Conversion mode: Within ±2% of rated voltage
Economy mode; Within -10% to +8% of rated voltage
- Rated output frequency[Hz]
- 50/60
- Output frequency regulation
- In Double Conversion mode fixed setting
Within ±1% of rated frequency
In automatic transfer setting: Within ±1/3/5% of rated frequency (Factory setting: ±3%)
During battery operation: Within ±0.5% of rated frequency (This applies in asynchronous operation too)
- Output transient voltage fluctuation
- At abrupt load change: Within ±5% of rated voltage (For 0⇔100% load step changes)
At loss/return of input power: Within ±5% of rated voltage (At rated output)
At abrupt input voltage change: Within ±5% of rated voltage (For ±10% voltage changes)
- Output overcurrent protection
- Automatic transfer to bypass (With automatic retransfer function)
- Output overload capability
- ・Inverter: 105% (for 200 ms)
・Bypass: 200% (for 30 s), 800%(for 2 cycles)
- Energy storage device type
- Small-sized valve-regulated lead-acid (VRLA) battery
- Expected battery (device) life
- Approx. 5 years
- Standard backup time[min]
- 3 (5)
- Cooling method
- Forced air cooling
- Operating temperature range
- -10 ~+40℃
- Operating humidity range
- 20 to 90% (non-condensing)
- EMC standard
- VCCI Class A
FCC Part 15 Subpart B Class A
EN 62040-2 C2:2010
EN 55022:2010 Class A
EN 62040-2:2006
EN 55024:2010
- Acoustic noise[dB]
- 45
- Heat dissipation[W]
- 130
- Mass[kg]
- 15
Note 1: The battery backup time is calculated at a 25°C ambient temperature, 0.8 load power factor, using new, fully charged batteries. The value in parentheses is calculated at a load power factor of 0.7. Note 2: The acoustic noise is for when in Double Conversion mode.
Download Materials List
Materials | Material No. | File Size | Download Link |
---|---|---|---|
Catalog | Download | ||
設定メニュー説明書(装置レビジョンA ~ F) | M0012434 | 6.9 MB | Login required |
取扱説明書(装置レビジョン A ~ D) | M0012431 | 6.3 MB | Login required |
取扱説明書(装置レビジョン E ~ F) | M0012431B | 6.4 MB | Login required |
取扱説明書(装置レビジョン G ~ ) | M0020729 | 13.8 MB | Login required |
Setting Menu Manual ( Revision Character : A ~ F) | M0012435 | 6.8 MB | Login required |
Setting Menu Manual ( Revision Character : G ~ ) | M0020314 | 8.1 MB | Login required |
Instruction Manual ( Revision Character : A ~ D ) | M0012432 | 6.4 MB | Login required |
Instruction Manual ( Revision Character : E ~ F ) | M0012432B | 6.5 MB | Login required |
Instruction Manual ( Revision Character : G ~ ) | M0020730 | 9.7 MB | Login required |
Manuel des menus de reglage ( Revision Character : A ~ D ) | M0012436 | 6.9 MB | Login required |
Manuel des menus de reglage ( Revision Character : G ~ ) | M0020315 | 7.0 MB | Login required |
Instruction Manual ( Revision Character : A ~ D ) | M0012433 | 6.5 MB | Login required |
Manuel d'utilisation ( Revision Character : E ~ F ) | M0012433B | 6.8 MB | Login required |
Manuel d'utilisation ( Revision Character : G ~ ) | M0020731 | 10.1 MB | Login required |
Checking the UPS Revision Number | C0051781 | 504.7 KB | Download |
SANUPS SOFTWARE STANDALONE | Download |
If there are any differences in the descriptions in Japanese, English or French, Japanese shall prevail.
Applicable Models
Model no. | Item Name |
---|---|
PMS52A00DL | UPS management software (Windows version) SANUPS SOFTWARE Download version |
PMS52A00DL-10 | UPS management software (Windows version, 10 licenses) SANUPS SOFTWARE Download version |
PMS52A00DL-100 | UPS management software (Windows version, 100 licenses) SANUPS SOFTWARE Download version |
PMS52A00DL-50 | UPS management software (Windows version, 50 licenses) SANUPS SOFTWARE Download version |
PMS53A00DL | UPS management software (Multi-OS version) SANUPS SOFTWARE Download version |
PMS53A00DL-10 | UPS management software (Multi-OS version, 10 licenses) SANUPS SOFTWARE Download version |
PMS53A00DL-100 | UPS management software (Multi-OS version, 100 licenses) SANUPS SOFTWARE Download version |
PMS53A00DL-50 | UPS management software (Multi-OS version, 50 licenses) SANUPS SOFTWARE Download version |
PRCONIF007 | Dry contact interface card (Terminal block) |
PRCONIF008 | Dry contact interface card (D-sub 15-pin) |
PRLANIF013B | Power Management Product - LAN Interface Card (Supports IPv6 and temperature/humidity sensors) |
PRLANIF022A | Power Management Product - LAN Interface Card (IPv6, Modbus TCP supported, with cover) |
PRLANIF024A | Power Management Product - LAN Interface Card (IPv6, Modbus TCP/RTU supported, with cover) |
PRLANIF031 | Power Management Product - LAN Interface Card (1-Gigabit Ethernet Supported) |
Related Information
Options
Item Name |
---|
Vertical stands (STAND2UA00) |
Floor mounting brackets (FM2UA00) |
Rack support rails (RM030) |
Air filter(FL011) |