Voltage Dip Compensator SANUPS C23A
C23A104C
- Eco Products
- Vertical type
- Input terminal block
- Output terminal block
- CE marking
- UKCA
For illustrative purposes only
Specifications
- Model No.
- C23A104C
- UPS topology
- Parallel processing
- No. of input phases/wires
- 3-phase 3-wire
- Rated input voltage[V]
- 200/210/220
- Rated input frequency[Hz]
- 50/60
- Input power factor
- 0.98 or greater (at rated output)
- No. of output phases/wires
- 3-phase 3-wire
- Rated output capacity[kVA]
- 100
- Rated output capacity[kW]
- 80
- Rated output voltage[V]
- 200/210/220
- Output voltage regulation
- During grid operation: Within -8% to +10% of rated voltage (This is the factory setting can be changed with settings.) During capacitor operation: Within ±2% of rated voltage
- Rated output frequency[Hz]
- 50/60
- Output frequency regulation
- During grid operation: Within ±4% of rated frequency During capacitor operation: Within ±0.1% of rated frequency
- Output transient voltage fluctuation
- During capacitor operation Variation rate: ±5% max. Settling time: 50 ms or less
- Output overcurrent protection
- The inverter shuts down at 110% of rated output, and then grid power will be directly supplied.
- Output overload capability
- Bypass circuit 200% (for 30 s), 800% (for 0.5 s)
- Output transfer time
- 0 s (no interruption)
- Energy storage device type
- Electric double layer capacitor (EDLC)
- Cooling method
- Forced air cooling
- Operating temperature range
- 0 ~ +40℃
- Operating humidity range
- 30 to 90% (non-condensing)
- Acoustic noise[dB]
- 65
- Heat dissipation[W]
- 5100
- Mass[kg]
- 670
- Remarks
- Dipcompensationtime: 1 s or more
Download Materials List
Materials | Material No. | File Size | Download Link |
---|---|---|---|
Catalog | Download |