Online UPS SANUPS A11N-Li
S-A11NL103A010Z
- Eco Products
- Vertical type
- Input terminal block
- Output terminal block

For illustrative purposes only
Specifications
- Model No.
- S-A11NL103A010Z
- UPS topology
- Double conversion online
- No. of input phases/wires
- Single-phase 2-wire
- Rated input voltage[V]
- 200
- Input voltage range
- Within -40 to +15% of rated voltage
- Rated input frequency[Hz]
- 50/60
- Input power factor
- 0.95 or greater
- Required input capacity[kVA]
- N-unit config.: 12 kVA or less
N+1-unit config.: 6.7 kVA or less
- No. of output phases/wires
- Single-phase 2-wire or single-phase 3-wire
- Rated output capacity[kVA]
- 10
- Rated output capacity[kW]
- 9
- Rated output voltage[V]
- 100 (2-wire) or 100/200 (3-wire)
- Output voltage regulation
- Within ±5% of rated voltage
- Rated output frequency[Hz]
- 50/60
- Output frequency regulation
- During grid operation: Within ±1/3/5% of rated frequency (Factory setting: ±3%)
During battery operation: Within ±0.5% of rated frequency
- Output transient voltage fluctuation
- Abrupt load change: Within ±5% of rated voltage (For 20⇔100% abrupt change)
Loss/return of input power: Within ±5% of rated voltage
Abrupt input voltage change: Within ±5% of rated voltage (For ±10% abrupt change)
- Output overcurrent protection
- N-unit config.: 104% or more
N+1-unit config.: 208% or more (Automatic transfer to bypass)
- Output overload capability
- Inverter N-unit config.: 104% (for 1 min), 112% (instantly)
Inverter N+1-unit config.: 208% (for 1 min), 224% (instantly)
Bypass N-unit config.: 200% (for 30 s), 800% (for 2 cycles)
Bypass N+1-unit config.: 400% (for 30 s), 1600% (for 2 cycles)
- Inverter
- High-frequency PWM
- Energy storage device type
- Lithium-ion battery
- Expected battery (device) life
- 10 years (At a 25 ºC ambient temperature. For reference purposes only.)
- Standard backup time[min]
- 10
- Cooling method
- Forced air cooling
- Operating temperature range
- -10 ~ +55℃
- Operating humidity range
- 10 to 90% (non-condensing)
- Acoustic noise[dB]
- 55
- Heat dissipation[W]
- 1000
- Mass[kg]
- 296